EuroWire May 2016
News Corporate
ACI’s warning on LSF cables
• BS 6724 – Armoured 1kV cables (only tested for pH and conductivity of smoke and not specifically for halogens) • BS 8573 – Non-armoured 1kV cables (only tested for pH and conductivity of smoke and not specifically for halogens The most relevant standards that cables might need to conform to in order to achieve LSHF rating are:
With the terms LSF and LSHF often interchanged due to the misconception that they are acronyms for the same thing, the Approved Cables Initiative (ACI) is warning contractors and installers to be cautious of cable labelled or described as LSF as this does not mean “halogen-free”. The ACI believes that the two terms – LSF and LSHF – are routinely and sometimes deliberately misused, and contractors wanting to purchase halogen-free cable should look for LSHF (or manufacturers’ equivalents) to ensure compliance. LSF (Low Smoke and Fume) was developed nearly 40 years ago in response to a demand for a cable product that, if burned, offered lower hazard levels than existing PVC. Such materials were a first attempt to answer the call for cables which would give off lower amounts of acidic and corrosive gases in a fire, but these cables were not and are still not halogen free. LSHF (Low Smoke Halogen-Free) materials have excellent flame resistance but, when affected by fire, have low emission of smoke and low emission of corrosive gases or have halogen-free materials. Such materials are not based on PVC. In the UK, LSHF cables for fixed wiring applications are most commonly available to the following standards: • BS EN 50525-3-41 – Single core wiring cables (although the standard does not include chemical tests for halogens specifically) • BS 7211 – Flat wiring cables (only tested for pH and conductivity of smoke and not specifically for halogens)
• • BS EN 61034-2 (smoke emission) BS EN 60754-2 (pH and conductivity) • BS EN 50525-1/BS EN 60754-1 (halogens)
BS 7671 (The Wiring Regulations) gives in Table 4A3 of the edition amended in 2015, a complete list of the specified standards with suitable cables for fixed wiring. All of these are either LSHF or PVC types. There are none that relate to the original concept of LSF. To be sure of the correct cable choice where Low Smoke Halogen-Free is specified, the ACI is advising contractors and installers to: • Check that your LSHF is genuinely halogen-free and is manufactured to the appropriate standard • Avoid anything described as “Low Smoke and Fume” or just LSF • Look for independent third party approval via bodies such as BASEC. Approved Cables Initiative – UK Website : www.aci.org.uk
14
www.read-eurowire.com
May 2016
Made with FlippingBook